3. INTERFACING THE PROTONODE TO THE AERCO CONTROL SYSTEM (ACS, BMS II, OR

BMS)

3.1 ProtoNode RER and LER showing connection ports

Figure 4. ProtoNode BACnet RER (left) and LonWorks LER (right)

3.2 ACS/BMS II/BMS Wiring Connections to ProtoNode RER and LER

• When an ACS, BMS II, or BMS is being used, an RS-485-to-RS-232 converter will be required to

connect it to the ProtoNode’s RS485 port (green 6-pin Phoenix connector).

• Refer to Figures 5 and 6 to locate the internal RS-232 connector JP12 (BMS) or JP5 (BMS II/ACS) inside

the wiring area of the ACS/BMS II/BMS.

• If the AERCO RS232-to-RS485 Converter (part no. 124943) is used, the RS-232 side of the converter

contains a connector that plugs directly into header connector JP12 (BMS) or JP5 (BMS II/ACS).

• If a third party converter is used, connect the RS-232 Receive (RxD) and Transmit (TxD) wire leads to

the internal RS-232 connector (JP12 or JP5) as shown in Figures 5 and 6. DO NOT connect the wire
shield on this side of the converter.

NOTE

If a third-party RS232-to-RS485 Converter is used, consult the manufacturer’s instruction manual for signal

polarity.

• On the RS-485 side of the converter (Figure 5 to Figure 7), connect the wire leads as follows:

o

Connect the TD B (+) terminal to the ProtoNode’s RS485+ Port.

o

Connect the TD A (-) terminal to the ProtoNode’s RS485- Port.

o

Connect the GND terminal to the ProtoNode’s RS485 Frame GND Port.

LonWorks

Port

LonWorks

Service Pin

RS-485 Port for Serial

Field Protocol

OEM connection

RS-485 Port

10/100

Base T

10/100

Base T

OEM

Connection

RS-485 Port

Power +/- and FG

(Frame Ground)

9-30 VDC, 12-24 VAC

Power +/- and FG

(Frame Ground)

9-30 VDC, 12-24 VAC