2. BACNET/LONWORKS SETUP THROUGH PROTOCESSOR PROTONODE RER/LER

2.1 Installation Steps For The Customer

1. Set the A, B, and S DIP Switch banks for field protocol baud rate, Node-ID/Device Instance, and proper

configuration. See Section 2.3.

2. Connect the ProtoNode to the Field protocol port and AERCO’s Control System/Boiler Management

System – RS-232 or RS-485 interface. See Section 3.

3. Power up the ProtoNode RER or LER. After power up, the device is installed on BACnet MS/TP, Metasys

N2, or LonWorks for the LER.

4. Where the Field protocol is BACnet/IP, refer to Section 5 to run the Ruinet utility program to change the

IP address. No changes to the configuration file are necessary.

2.2 Record Identification Data

Each ProtoNode has a unique serial number located on the underside of the unit. The number format is FPC-N3X-
XXX-XXX-XXXX. This number should be recorded as it may be required for technical support. The AERCO part
numbers and model numbers are shown in the table below:

ProtoNode Model AERCO P/N

Model Number

RER

64084

FPC-N34-103-126-0645

LER

64085

FPC-N35-103-401-0646

2.3 Configure the DIP Switches

2.3.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7) for BACnet MS/TP,

BACnet/IP, and Metasys N2

• The A Bank DIP switches on the ProtoNode RER-R allow users to set the Node-ID/Device Instance

on the Field RS-485.

• DIP switches A0 – A7 can also be used to set the MAC Address for BACnet MS/TP and BACnet/IP

Figure 1. A0 – A7 DIP Switches

• Please refer to Appendix B.2 for the full range of addresses to set Nod-ID/Device Instance..

2.3.2 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP & Metasys N2

• Setting the serial baud rate to match the baud rate provided by the Building Management

System can be done through DIP Switches B0 – B3 for BACnet MS/TP.

• Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.