1 baud rate dip switch selection, Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 8

Page 8 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
B0 B1 B2 B3
Figure 2. B0 – B3 DIP Switches
2.3.2.1 Baud Rate DIP Switch Selection
Baud
B0
B1
B2
B3
Auto
Off Off Off Off
9600
On On On Off
19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
2.3.3 Using S0 – S3 bank of DIP Switches to select and load Configuration Files
• The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode RER (BACnet MS/TP,
BACnet/IP, Modbus TCP and/or Metasys N2) and LER (LonWorks).
S0 S1 S2 S3
Figure 3. S0 – S3 DIP Switches