1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2 ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
Blr Addr 12
01-Fire Rate Out
boilerstate_12
AV:111
data float
111
nvoBlrState12
inc count (9)
Output (non-polled)
30009/12
02-Active Setpoint
effectsetpt_12
AV:112
data float
112
nvoEffSetpt12
inc count (9)
Output (non-polled)
30017/12
03-Net Remote Setpt
setpt_12
AV:113
data float
113
nviSetpt12
inc count (9)
Input (non-polling)
40001/12
05-Fire Rate In
boilerload_12
AV:115
data float
115
nvoBlrLoad12
inc count (9)
Output (non-polled)
30018/12
06-Outlet Temp
localsuptemp_1
2
AV:116
data float
116
nvoLocSupTmp
12
inc count (9)
Output (non-polled)
30003/12
07-Display Code
dispcode_12
AV:117
data float
117
nvoDispCode1
2
inc count (9)
Output (non-polled)
30001/12
08-Unit Status
unitstat_12
AV:118
data float
118
nvoUnitStat12
inc count (9)
Output (non-polled)
30002/12
09-Run Cycles
runcycles_12
AV:119
data float
119
nvoRunCycles1
2
51
Output (non-polled)
30012-30013/12
10-Run Hours
runhours_12
AV:120
data float
120
nvoRunHours1
2
51
Output (non-polled)
30014-30015/12
Mlx Addr 13
01-Act Mod Lev
boilerstate_13
AV:121
data float
121
nvoMlxState13
inc count (9)
Output (non-polled)
41009/13
02-Target Setpoint
effectsetpt_13
AV:122
data float
122
nvoMlxSetpt13
inc count (9)
Output (non-polled)
41019/13
03-Req Outlet Temp
setpt_13
AV:123
data float
123
nviMlxSetptRq1
3
inc count (9)
Input (non-polling)
41005/13
04-Net Direct Drive
boilercmd_13
AV:124
data float
124
nviMlxCmd13
inc count (9)
Input (non-polling)
40002/13
05-Mod Lev In
boilerload_13
AV:125
data float
125
nvoMlxLoad13
inc count (9)
Output (non-polled)
41201/13
06-Flow Sens Temp
localsuptemp_1
3
AV:126
data float
126
nvoMlxSupTmp
13
inc count (9)
Output (non-polled)
41003/13
07-Display Code
dispcode_13
AV:127
data float
127
nvoMlxDispCod
e13
inc count (9)
Output (non-polled)
30001/13
11-Error Code
errcode_13
AV:128
data float
128
nvoMlxErrCode
13
51
Output (non-polled)
40001/13
08-Unit Status
unitstat_13
AV:129
data float
129
nvoMlxStat13
inc count (9)
Output (non-polled)
30002/13