Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 54

Advertising
background image

Page 54 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

Equipment

Point Name

Name

Read
Only

BACnet
Type:ID

N2 Type

N2 ID

Lon SNVT
NAME

Lon SNVT

Lon Direction

ModBus/Unit
Address

Blr Addr 12

01-Fire Rate Out

boilerstate_12

AV:111

data float

111

nvoBlrState12

inc count (9)

Output (non-polled)

30009/12

02-Active Setpoint

effectsetpt_12

AV:112

data float

112

nvoEffSetpt12

inc count (9)

Output (non-polled)

30017/12

03-Net Remote Setpt

setpt_12

AV:113

data float

113

nviSetpt12

inc count (9)

Input (non-polling)

40001/12

05-Fire Rate In

boilerload_12

AV:115

data float

115

nvoBlrLoad12

inc count (9)

Output (non-polled)

30018/12

06-Outlet Temp

localsuptemp_1
2

AV:116

data float

116

nvoLocSupTmp
12

inc count (9)

Output (non-polled)

30003/12

07-Display Code

dispcode_12

AV:117

data float

117

nvoDispCode1
2

inc count (9)

Output (non-polled)

30001/12

08-Unit Status

unitstat_12

AV:118

data float

118

nvoUnitStat12

inc count (9)

Output (non-polled)

30002/12

09-Run Cycles

runcycles_12

AV:119

data float

119

nvoRunCycles1
2

51

Output (non-polled)

30012-30013/12

10-Run Hours

runhours_12

AV:120

data float

120

nvoRunHours1
2

51

Output (non-polled)

30014-30015/12

Mlx Addr 13

01-Act Mod Lev

boilerstate_13

AV:121

data float

121

nvoMlxState13

inc count (9)

Output (non-polled)

41009/13

02-Target Setpoint

effectsetpt_13

AV:122

data float

122

nvoMlxSetpt13

inc count (9)

Output (non-polled)

41019/13

03-Req Outlet Temp

setpt_13

AV:123

data float

123

nviMlxSetptRq1
3

inc count (9)

Input (non-polling)

41005/13

04-Net Direct Drive

boilercmd_13

AV:124

data float

124

nviMlxCmd13

inc count (9)

Input (non-polling)

40002/13

05-Mod Lev In

boilerload_13

AV:125

data float

125

nvoMlxLoad13

inc count (9)

Output (non-polled)

41201/13

06-Flow Sens Temp

localsuptemp_1
3

AV:126

data float

126

nvoMlxSupTmp
13

inc count (9)

Output (non-polled)

41003/13

07-Display Code

dispcode_13

AV:127

data float

127

nvoMlxDispCod
e13

inc count (9)

Output (non-polled)

30001/13

11-Error Code

errcode_13

AV:128

data float

128

nvoMlxErrCode
13

51

Output (non-polled)

40001/13

08-Unit Status

unitstat_13

AV:129

data float

129

nvoMlxStat13

inc count (9)

Output (non-polled)

30002/13

C.2.6 - Twelve C-Mores, Six ECS/SP, Four Modulex, and Two ACS/BMS II (Cont.)

Advertising