Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 51

Advertising
background image

Page 51 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

Equipment

Point Name

Name

Read
Only

BACnet
Type:ID

N2 Type

N2 ID

Lon SNVT
NAME

Lon SNVT

Lon Direction

ModBus/Unit
Address

Blr Addr 6

01-Fire Rate Out

boilerstate_6

AV:51

data float

51

nvoBlrState6

inc count (9)

Output (non-polled)

30009/6

02-Active Setpoint

effectsetpt_6

AV:52

data float

52

nvoEffSetpt6

inc count (9)

Output (non-polled)

30017/6

03-Net Remote Setpt

setpt_6

AV:53

data float

53

nviSetpt6

inc count (9)

Input (non-polling)

40001/6

05-Fire Rate In

boilerload_6

AV:55

data float

55

nvoBlrLoad6

inc count (9)

Output (non-polled)

30018/6

06-Outlet Temp

localsuptemp_6

AV:56

data float

56

nvoLocSupTmp
6

inc count (9)

Output (non-polled)

30003/6

07-Display Code

dispcode_6

AV:57

data float

57

nvoDispCode6

inc count (9)

Output (non-polled)

30001/6

08-Unit Status

unitstat_6

AV:58

data float

58

nvoUnitStat6

inc count (9)

Output (non-polled)

30002/6

09-Run Cycles

runcycles_6

AV:59

data float

59

nvoRunCycles6

51

Output (non-polled)

30012-30013/6

10-Run Hours

runhours_6

AV:60

data float

60

nvoRunHours6

51

Output (non-polled)

30014-30015/6

Blr Addr 7

01-Fire Rate Out

boilerstate_7

AV:61

data float

61

nvoBlrState7

inc count (9)

Output (non-polled)

30009/7

02-Active Setpoint

effectsetpt_7

AV:62

data float

62

nvoEffSetpt7

inc count (9)

Output (non-polled)

30017/7

03-Net Remote Setpt

setpt_7

AV:63

data float

63

nviSetpt7

inc count (9)

Input (non-polling)

40001/7

05-Fire Rate In

boilerload_7

AV:65

data float

65

nvoBlrLoad7

inc count (9)

Output (non-polled)

30018/7

06-Outlet Temp

localsuptemp_7

AV:66

data float

66

nvoLocSupTmp
7

inc count (9)

Output (non-polled)

30003/7

07-Display Code

dispcode_7

AV:67

data float

67

nvoDispCode7

inc count (9)

Output (non-polled)

30001/7

08-Unit Status

unitstat_7

AV:68

data float

68

nvoUnitStat7

inc count (9)

Output (non-polled)

30002/7

09-Run Cycles

runcycles_7

AV:69

data float

69

nvoRunCycles7

51

Output (non-polled)

30012-30013/7

10-Run Hours

runhours_7

AV:70

data float

70

nvoRunHours7

51

Output (non-polled)

30014-30015/7

C.2.6 - Twelve C-Mores, Six ECS/SP, Four Modulex, and Two ACS/BMS II (Cont.)