Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 43

Advertising
background image

Page 43 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

Equipment

Point Name

Name

Read
Only

BACnet Type:ID

N2 Type

N2 ID

Lon SNVT NAME

Lon SNVT

Lon Direction

ModBus/Unit
Address

Blr Addr 10

01-Fire Rate Out

boilerstate_10

AV:130

data float

91

nvoBlrState10

inc count (9)

Output (non-polled)

30009/10

02-Active Setpoint

effectsetpt_10

AV:131

data float

92

nvoEffSetpt10

inc count (9)

Output (non-polled)

30017/10

03-Net Remote Setpt

setpt_10

AV:132

data float

93

nviSetpt10

inc count (9)

Input (non-polling)

40001/10

05-Fire Rate In

boilerload_10

AV:124

data float

95

nvoBlrLoad10

inc count (9)

Output (non-polled)

30018/10

06-Outlet Temp

localsuptemp_10

AV:125

data float

96

nvoLocSupTmp10

inc count (9)

Output (non-polled)

30003/10

07-Display Code

dispcode_10

AV:126

data float

97

nvoDispCode10

inc count (9)

Output (non-polled)

30001/10

08-Unit Status

unitstat_10

AV:127

data float

98

nvoUnitStat10

inc count (9)

Output (non-polled)

30002/10

09-Run Cycles

runcycles_10

AV:128

data float

99

nvoRunCycles10

51

Output (non-polled)

30012-30013/10

10-Run Hours

runhours_10

AV:129

data float

100

nvoRunHours10

51

Output (non-polled)

30014-30015/10

Blr Addr 11

01-Fire Rate Out

boilerstate_11

AV:140

data float

101

nvoBlrState11

inc count (9)

Output (non-polled)

30009/11

02-Active Setpoint

effectsetpt_11

AV:141

data float

102

nvoEffSetpt11

inc count (9)

Output (non-polled)

30017/11

03-Net Remote Setpt

setpt_11

AV:142

data float

103

nviSetpt11

inc count (9)

Input (non-polling)

40001/11

05-Fire Rate In

boilerload_11

AV:134

data float

105

nvoBlrLoad11

inc count (9)

Output (non-polled)

30018/11

06-Outlet Temp

localsuptemp_11

AV:135

data float

106

nvoLocSupTmp11

inc count (9)

Output (non-polled)

30003/11

07-Display Code

dispcode_11

AV:136

data float

107

nvoDispCode11

inc count (9)

Output (non-polled)

30001/11

08-Unit Status

unitstat_11

AV:137

data float

108

nvoUnitStat11

inc count (9)

Output (non-polled)

30002/11

09-Run Cycles

runcycles_11

AV:138

data float

109

nvoRunCycles11

51

Output (non-polled)

30012-30013/11

10-Run Hours

runhours_11

AV:139

data float

110

nvoRunHours11

51

Output (non-polled)

30014-30015/11

Blr Addr 12

01-Fire Rate Out

boilerstate_12

AV:150

data float

111

nvoBlrState12

inc count (9)

Output (non-polled)

30009/12

02-Active Setpoint

effectsetpt_12

AV:151

data float

112

nvoEffSetpt12

inc count (9)

Output (non-polled)

30017/12

03-Net Remote Setpt

setpt_12

AV:152

data float

113

nviSetpt12

inc count (9)

Input (non-polling)

40001/12

05-Fire Rate In

boilerload_12

AV:144

data float

115

nvoBlrLoad12

inc count (9)

Output (non-polled)

30018/12

06-Outlet Temp

localsuptemp_12

AV:145

data float

116

nvoLocSupTmp12

inc count (9)

Output (non-polled)

30003/12

07-Display Code

dispcode_12

AV:146

data float

117

nvoDispCode12

inc count (9)

Output (non-polled)

30001/12

08-Unit Status

unitstat_12

AV:147

data float

118

nvoUnitStat12

inc count (9)

Output (non-polled)

30002/12

09-Run Cycles

runcycles_12

AV:148

data float

119

nvoRunCycles12

51

Output (non-polled)

30012-30013/12

10-Run Hours

runhours_12

AV:149

data float

120

nvoRunHours12

51

Output (non-polled)

30014-30015/12


C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)