5 c-more, Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 14

Advertising
background image

Page 14 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

.5 C-MORE













Figure 8a. RS-485 Connection to C-MORE (RS-485)

IMPORTANT NOTE

The 4-position RS485 DIP Switch (S2) on the PMC PCB of the C-More Controller must be set as
follows:

1) The termination (TERM) and bias (BIAS1 & BIAS2) DIP Switches of S2 must be set to DISABLE.

2) If an Oxygen Sensor is connected to the C-More Controller, switch R1 (see below) should be set

to DISABLED (down). If an Oxygen Sensor is NOT connected to the C-More Controller, it should
be set to ENABLED (up). Improper setting of R1 may result in error messages.

Instructions for accessing the PMC PCB and this DIP Switch can be found in Section 4.3 of ModBus
manual GF-114.

















C-More Controller PMC PCB

If an Oxygen Sensor is attached to the C-
More Controller, set R1 to DISABLED
(down). If an Oxygen Sensor is NOT used,
set R1 to ENABLED (up). Factory default
setting is ENABLED.

ENABLE

DISABLE

BI

AS

2

T

ERM

BI

AS1

R1

S2

RS485

TERMINATE SHIELD

TO SIGNAL GROUND

TIE TOGETHER WITH

SHIELDS OF OTHER

UNITS AND

FLOAT AT END OF

LINE (INSULATE)

TERMINATE SHIELD

TO SIGNAL GROUND

R1