Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 22
 
Page 22 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1 
GF-129
A.1.2 - ProtoNode RER - LED Locations and Functions
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 16. AERCO/ProtoNode Gateway RER Indication LED Locations
LED
DESCRIPTION
PWR
This is the power light and should show steady green at all times when the ProtoNode RER is 
powered. 
System
Error
The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady 
red light will indicate there is a system error on the ProtoCessor. If this occurs, immediately report the 
related “system error” shown in the error screen of the RUI interface to AERCO International for 
evaluation. 
Comm.
Error
COMM ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady 
red light will indicate the communications problem if there is a configured node connected to the 
ProtoCessor that is offline. To establish the cause of the error, go to the error screen of the RUI 
interface. 
Config.
Error
Config ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady 
amber light will indicate a configuration error exists in the active configuration. See the Error Screen 
in the Remote User Interface for a description of the configuration error. 
Node
Offline
Node Offline LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. If the 
Node Offline LED stays on solid, a node offline condition has occurred. 
Unused
15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds, then turn off.
RX
On normal operation of FPC-FD2, the RX LED will flash when a message is received on the field port of 
the ProtoCessor. 
TX
On normal operation of FPC-FD2, the TX LED will flash when a message is sent on the field port of the 
ProtoCessor 
Run
RUN LED will flash 20 seconds after power up, signifying normal operation. The ProtoNode RER will be 
able to access RUINET once this LED starts flashing. During the first 20 seconds, the LED should be off 
Unused
Power
Power
Node 
Offline 
Config.
Error
Comm.
Error
System
Error
TX
RX
Run