Page 22 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

A.1.2 - ProtoNode RER - LED Locations and Functions



















Figure 16. AERCO/ProtoNode Gateway RER Indication LED Locations

LED

DESCRIPTION

PWR

This is the power light and should show steady green at all times when the ProtoNode RER is
powered.

System

Error

The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady
red light will indicate there is a system error on the ProtoCessor. If this occurs, immediately report the
related “system error” shown in the error screen of the RUI interface to AERCO International for
evaluation.

Comm.

Error

COMM ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady
red light will indicate the communications problem if there is a configured node connected to the
ProtoCessor that is offline. To establish the cause of the error, go to the error screen of the RUI
interface.

Config.

Error

Config ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady
amber light will indicate a configuration error exists in the active configuration. See the Error Screen
in the Remote User Interface for a description of the configuration error.

Node

Offline

Node Offline LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. If the
Node Offline LED stays on solid, a node offline condition has occurred.

Unused

15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds, then turn off.

RX

On normal operation of FPC-FD2, the RX LED will flash when a message is received on the field port of
the ProtoCessor.

TX

On normal operation of FPC-FD2, the TX LED will flash when a message is sent on the field port of the
ProtoCessor

Run

RUN LED will flash 20 seconds after power up, signifying normal operation. The ProtoNode RER will be
able to access RUINET once this LED starts flashing. During the first 20 seconds, the LED should be off

Unused

Power

Power

Node
Offline

Config.

Error

Comm.

Error

System

Error

TX

RX

Run