Appendix C. CONFIGURATION INFORMATION

C.1 Default Modbus RTU COM Settings for AERCO Controllers

Serial Port Setting

ACS, BMS II, BMS

ECS/SP

BCM

(Modulex)

C-More

Baud Rate

≤19200

≤38.4

9600

9600

Data Bits

8

8

8

8

Stop Bits

1

1

1

1

Parity

None

None

None

None

Configuration

Controllers

Modbus Default

Address

12

C-More

Controllers

&

1 ACS/BMS II/BMS

C-more 1

1

C-more 2

2

C-more 3

3

C-more 4

4

C-more 5

5

C-more 6

6

C-more 7

7

C-more 8

8

C-more 9

9

C-more 10

10

C-more 11

11

C-more 12

12

ACS /BMS II/BMS

128

4

Modulex

Controllers

&

1 ACS/BMS II

Modulex 1

1

Modulex 2

2

Modulex 3

3

Modulex 4

4

ACS /BMS II/BMS

128

4

ECS/SP

ECS 1

29

ECS 2

30

ECS 3

31

ECS 4

32


For Profiles defined in Section C.2.6, the ECS/SP Modbus default point addresses are defined below.

Configuration

Controllers

Modbus Default

Address

6

ECS/SP

ECS 1

17

ECS 2

18

ECS 3

19

ECS 4

20

ECS 5

21

ECS 6

22