• If the IP Address of the ProtoNode module appears on the screen, the ProtoNode is running.
Figure 12. RUIPING screen
5.2 Connect to the ProtoNode using RUI (Ruinet)
• Double click on the debugging utility, “RUINET” (Remote User Interface). The following screen will
appear: (if Ruinet does not automatically display the main menu, select the ProtoNode by typing the
2-digit number to the left of the title name).
Figure 13. RUINET screen
5.3 Set IP Address for BACnet/IP
• From the main menu, press “I” to enter the Edit IP Address Settings menu
• Press “1” to modify the IP address of the Ethernet adapter
• Type in a new IP address in the format 192.168.2.X and press <Enter>
• If necessary, press “2” to and change the netmask
• Type in a new Subnet Mask and press <Enter>