AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

Equipment

Point Name

Name

Read
Only

BACnet
Type:ID

N2 Type

N2 ID

Lon SNVT NAME

Lon SNVT

Lon Direction

ModBus/Unit Address

05-Mod Lev In

boilerload_2

AV:148

data float

157

nvoMlxLoad2

inc count (9)

Output (non-polled)

41201/2

06-Flow Sens Temp

localsuptemp_2

AV:149

data float

158

nvoMlxSupTmp2

inc count (9)

Output (non-polled)

41003/2

07-Display Code

dispcode_2

AV:150

data float

159

nvoMlxDispCode2

inc count (9)

Output (non-polled)

30001/2

11-Error Code

errcode_2

AV:4

data float

160

nvoMlxErrCode2

51

Output (non-polled)

40001/2

08-Unit Status

unitstat_2

AV:151

data float

161

nvoMlxStat2

inc count (9)

Output (non-polled)

30002/2

09-Ret Flow Temp

returntemp_2

AV:5

data float

162

nvoMlxRetTmp2

inc count (9)

Output (non-polled)

41004/2

Mlx Addr 3

01-Act Mod Lev

boilerstate_3

AV:18

data float

164

nvoMlxState3

inc count (9)

Output (non-polled)

41009/3

02-Target Setpoint

effectsetpt_3

AV:19

data float

165

nvoMlxSetpt3

inc count (9)

Output (non-polled)

41019/3

03-Req Outlet Temp

setpt_3

AV:20

data float

166

nviMlxSetptRq3

inc count (9)

Input (non-polling)

41005/3

04-Net Direct Drive

boilercmd_3

AV:21

data float

167

nviMlxCmd3

inc count (9)

Input (non-polling)

40002/3

05-Mod Lev In

boilerload_3

AV:22

data float

168

nvoMlxLoad3

inc count (9)

Output (non-polled)

41201/3

06-Flow Sens Temp

localsuptemp_3

AV:23

data float

169

nvoMlxSupTmp3

inc count (9)

Output (non-polled)

41003/3

07-Display Code

dispcode_3

AV:24

data float

170

nvoMlxDispCode3

inc count (9)

Output (non-polled)

30001/3

11-Error Code

errcode_3

AV:7

data float

171

nvoMlxErrCode3

51

Output (non-polled)

40001/3

08-Unit Status

unitstat_3

AV:25

data float

172

nvoMlxStat3

inc count (9)

Output (non-polled)

30002/3

09-Ret Flow Temp

returntemp_3

AV:8

data float

173

nvoMlxRetTmp3

inc count (9)

Output (non-polled)

41004/3

Mlx Addr 4

01-Act Mod Lev

boilerstate_4

AV:28

data float

175

nvoMlxState4

inc count (9)

Output (non-polled)

41009/4

02-Target Setpoint

effectsetpt_4

AV:29

data float

176

nvoMlxSetpt4

inc count (9)

Output (non-polled)

41019/4

03-Req Outlet Temp

setpt_4

AV:30

data float

177

nviMlxSetptRq4

inc count (9)

Input (non-polling)

41005/4

04-Net Direct Drive

boilercmd_4

AV:42

data float

178

nviMlxCmd4

inc count (9)

Input (non-polling)

40002/4

05-Mod Lev In

boilerload_4

AV:43

data float

179

nvoMlxLoad4

inc count (9)

Output (non-polled)

41201/4

06-Flow Sens Temp

localsuptemp_4

AV:44

data float

180

nvoMlxSupTmp4

inc count (9)

Output (non-polled)

41003/4

07-Display Code

dispcode_4

AV:45

data float

181

nvoMlxDispCode4

inc count (9)

Output (non-polled)

30001/4

11-Error Code

errcode_4

AV:10

data float

182

nvoMlxErrCode4

51

Output (non-polled)

40001/4

08-Unit Status

unitstat_4

AV:46

data float

183

nvoMlxStat4

inc count (9)

Output (non-polled)

30002/4

09-Ret Flow Temp

returntemp_4

AV:11

data float

184

nvoMlxRetTmp4

inc count (9)

Output (non-polled)

41004/4



C.2.4 Modulex and One ACS/BMS II (Cont.)