7 condensate drain trap – AERCO BMK 2000DF User Manual

Page 100

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 7 – MAINTENANCE

Page 100 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

7.7 CONDENSATE DRAIN TRAP

Benchmark boilers contains a condensate trap as shown in Chapter 2, Figure 2-5. The trap is

located external to the unit and attached to the drain pipe from the exhaust manifold. This trap

should be inspected and cleaned in accordance with the maintenance schedule shown in Table

7-1 to ensure proper operation. To inspect and clean the trap, proceed as follows:

Condensate Drain Trap Maintenance Procedure

1.

Disconnect the external condensate trap by loosening the union pipe connection between

the trap and the exhaust manifold drain pipe.

2.

Remove the connections on the inlet and outlet sides of the condensate trap shown in

Figure 7-6.

3.

Loosen the four (4) thumbscrews securing the cover on the condensate trap. Remove the

cover.

4.

Remove the float from the condensate trap.

5.

Remove the O-ring and orifice gaskets from the trap. AERCO recommends that these

items be replaced annually.

6.

Thoroughly clean the trap and float. Also inspect the drain piping for blockage. If the trap

cannot be thoroughly cleaned, replace the trap.

7.

After the above items have been inspected and thoroughly cleaned, replace the O-ring

(84017) and orifice gasket (81092) with new parts.

8.

Reassemble all piping and hose connections to the condensate trap inlet and outlet.

Reconnect trap to exhaust manifold drain.

NOTE

T

here are two slightly different types of condensate traps that may be used in

your configuration; an older style with a separate inlet adapter, and a newer style

with a built-in adapter (see Figure 11). Maintenance is the same, except that the

newer style does not need an orifice gasket (Step 6).

9.

Figure 7-6: External Condensate Trap: Cutaway and Exploded Views

THUMB
SCREWS

COVER

GASKET

FLOAT
GUIDE

FLOAT

CONDENSATE

TRAP

(P/N 24060)

OUTLET

INLET

Thumb Screws

(4)

Condensate

Trap O-Ring

Float

Float Guide

O-Rings

(2)

3/4" NPT Port

3/4" NPT Port

Adapter

Opening

Advertising