CHAPTER 2 – INSTALLATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 21 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

While observing the above guidelines, install the condensate trap as follows:

Condensate Trap Installation

1. Connect the condensate trap inlet to the exhaust manifold drain connection by inserting

the drain port directly into the trap adaptor inlet, and then tightening the inlet thumbscrew,

as shown in Figure 2-6. The inlet features two integral O-rings to prevent leakage.

2. At the condensate trap outlet, install a 3/4” NPT nipple.
3. Connect a length of 1” diameter polypropylene hose to the trap outlet and secure with a

hose clamp.

4. Route the hose on the trap outlet to a nearby floor drain.

If a floor drain is not available, a condensate pump can be used to remove the condensate to

drain. The maximum condensate flow rate is 30 GPH. The condensate drain trap, associated

fittings and drain line must be removable for routine maintenance.

Use PVC, stainless steel, aluminum or polypropylene for condensate drain

piping (Figure 2-6). DO NOT use carbon or copper components.

Figure 2-6: Sample Condensate Trap Installation (Right Side View)

CAUTION

EXHAUST

MANIFOLD

DRAIN PORT

COMBUTION

ANALYZER

PROBE PORT

EXHAUST

MANIFOLD

3/4” NPT

NIPPLES

HOSE
CLAMP

T O

FLOOR

DRAIN

CONDENSATE

TRAP (P/N 24060)

TRAP INLET

INTEGRAL

ADAPTOR AND

THUMBSCREW

TOP

COVER

THUMB

SREWS

(4 ea.)

1” DIAM.

HOSE

NOTE

HOUSKEEPING

PAD MUST NOT

EXTEND

UNDER THE

CONDENSATE

ASSEMBLY.

4” MINIMUM

(8” MAXIMUM)

4”