1 outdoor air in (out) & air sensor common (com) – AERCO BMK 2000DF User Manual

Page 28

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 2 – INSTALLATION

Page 28 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

Figure 2-12: I/O Box Terminal Strips

2.10.1 Outdoor Air In (OUT)

& Air Sensor Common (COM)

The OUTDOOR AIR IN terminal is used for connecting an outdoor temperature sensor (AERCO

P/N GM-123525) as required primarily for the Indoor/Outdoor reset mode of operation. It can

also be used with another mode if it is desired to use the outdoor sensor enable/disable feature.

This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an

enable/disable outdoor temperature, see the Configuration Menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the

OUTDOOR AIR IN and AIR SENSOR COMMON terminals of the I/O PCB (Figure 2-12). Wire

the sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no polarity to

observe when terminating these wires. The shield is to be connected only to the terminals

labeled SHIELD in the I/O Box PCB. The sensor end of the shield must be left free and

ungrounded.
When mounting the sensor, it must be located on the North side of the building where an

average outside air temperature is expected. The sensor must be shielded from direct sunlight

as well as impingement by the elements. If a shield is used, it must allow for free air circulation.

Advertising
This manual is related to the following products: