2 combustion air terminal, 3 o2 sensor (o2+ & o2-), 4 spark signal (flw+ & flw-) – AERCO BMK 2000DF User Manual

Page 29: 5 analog in (+ & -), 6 b.m.s. (pwm) in (bms+ & bms-), 7 shield (shld & shld), 8 analog output (+ & -), Sensor (o2+ & o2-)

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 2 – INSTALLATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 29 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

2.10.2 COMBUSTION AIR Terminal

The COMBUSTIAN AIR terminal is used to monitor the combustion air temperature sensor. This

input is always enabled and is a “to view only” input that can be seen in the operating menu.

The sensor is an AERCO BALCO wire sensor P/N 12449. A resistance chart for this sensor is

provided in APPENDIX C. This sensor is an active part of the combustion control system and

must be operational for accurate air/fuel mixing control.

2.10.3 O

2

SENSOR

(O2+ & O2-)

The O

2

SENSOR (+) and O

2

SENSOR (–) terminals are used to connect an integrated oxygen

sensor to the I/O Box PCB. The O

2

concentration is displayed in the operating menu of the C-

More Control system after a 60 second warm-up period.

2.10.4 SPARK SIGNAL

(FLW+ & FLW-)

The two SPARK SIGNAL terminals permit an external current sensor to be connected for

ignition spark monitoring purposes. If no spark is present during the ignition sequence, the

controller will shut down and display a fault message.

2.10.5 Analog In

(+ & -)

The two ANALOG IN terminals are used when an external signal is used to change the setpoint

(Remote Setpoint Mode) of the boiler.
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA/ 0 to 5 VDC signal may be used to vary the set-

point or air/fuel valve position. The factory default setting is for 4 to 20 mA / 1 to 5 VDC,

however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu

described in Chapter 3.
If voltage rather than current is selected as the drive signal, a DIP switch must be set on the

PMC Board located inside the C-More Control Box. Contact the AERCO factory for information

on setting DIP switches.
All supplied signals must be floating (ungrounded) signals. Connections between the source

and the boiler’s I/O PCB (Figure 2-12) must be made using twisted shielded pair of 18–22 AWG

wire such as Belden 9841. Polarity must be maintained and the shield must be connected only

at the source end and must be left floating (not connected) at the Boiler’s I/O PCB.
Whether using voltage or current for the drive signal, they are linearly mapped to a 40°F to

240°F setpoint or a 0% to 100% air/fuel valve position. No scaling for these signals is provided

2.10.6 B.M.S. (PWM) In

(BMS+ & BMS-)

These terminals are only used to connect to legacy AERCO Boiler Management Systems

(BMS), which utilize a 12 millisecond, ON/OFF duty cycle and is Pulse Width Modulated (PWM)

to control valve position. A 0% valve position = a 5% ON pulse and a 100% valve position = a

95% ON pulse. Note that these connections cannot be used with the AERCO Control System

(ACS).

2.10.7 Shield

(SHLD & SHLD)

The SHIELD terminals are used to terminate any shields used on sensor wires connected to the

unit. Shields must only be connected to these terminals.

2.10.8 Analog Output (+ & -)

The ANALOG OUT terminals (+ & -) output from 0 to 20 mA and may be used to monitor

Setpoint, Outlet Temperature, Valve Position 4-20 mA, Valve Position 0-10v or be set to OFF.

Default setting in the C-More controller is Valve Position 0-10v and settings behave as follows:

Advertising
This manual is related to the following products: