Appendix A: Boiler Menu Item Descriptions – Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists

between the setpoint temperature and the actual outlet

temperature. If the actual error is less than the

proportional band setting (1 to 120°F), the fire rate will be

less than 100%. If the error is equal to or greater than

the proportional band setting, the fire rate will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint error,

to add or subtract from the output each minute to move

towards the setpoint. Gain is adjustable from 0.00 to

1.00 (Default is 1.0).

Derivative Time

This value (0.0 to 2.0 min.) responds to the rate of

change of the setpoint error. This is the time that this

action advances the output.

WARMUP

The feature embodied in the next three menu items

eliminates Temperature Overshoots during the “Warmup”

period of a cold ignition cycle on all boilers by temporarily

modifying the PID Gain parameter during warmup and

for a period defined in the Tuning Menu.

Warmup Prop Band

Range = 1-120

Default = 95

Warmup Int Gain

Range = 1-200

Default = 50

Warmup PID Timer

Range = 1-240

Default = 20

Reset Defaults?

Allows Tuning Menu options to be reset to their Factory

Default values.