Benchmark 1500DF - 2000DF Boilers

CHAPTER 3 – OPERATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 51 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

(b) The “Spark Cycle Time” item in the Factory menu can be set to either 0 Sec, 2 Sec

or 7 Sec to define the duration of the Spark Element Cleaning Cycle. This cycle

turns on the spark transformer to produce a spark (with no gas flowing) to clean the

spark element of moisture or carbon buildup.
For the duration of this cycle, the C-More will display the “CLEANING IGNITER”

message.

(c) Following the Spark Element Cleaning Cycle, power is applied to the Gas Safety

Shut-off Valve (SSOV) and the C-More displays the “PRE IGNITION” message.

When the SSOV indicates the Gas Valve is OPEN (POC), the C-More displays the

“IGNITION TRIAL” message.

(d) If no spark is present 3 seconds into the IGNITION TRIAL, the C-More will abort the

Ignition Cycle and shut down the boiler. Refer to Chapter 8: Troubleshooting for

guidance if this occurs.


Figure 3-6: Air/Fuel Valve In Ignition Position

6.

Up to 4 seconds will be allowed for ignition to be detected. The igniter relay will be turned

off one second after flame is detected.

7.

After 2 seconds of continuous flame, Flame Proven will be displayed and the flame

strength will be indicated. After 5 seconds, the current date and time will be displayed in

place of the flame strength.

8.

With the unit firing properly, it will be controlled by the temperature controller circuitry. The

boiler’s VALVE POSITION will be continuously displayed on the front panel bargraph.

Once the demand for heat has been satisfied, the Control Box will turn off the SSOV gas valve.

The blower relay will be deactivated and the Air/Fuel Valve will be closed. Standby will be

displayed.

TO BLOWER

AIR IN

IGNITION

VALVE POSITION

DIAL AT

25% to 35%

STEPPER
MOTOR