CHAPTER 5 – MODE OF OPERATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 73 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

5.5.1 Direct Drive Field Wiring

The only wiring connections necessary for Direct Drive mode are connection of the remote

signal leads from the source to the unit’s I/O Box. For either a 4-20mA/0-5V or a 0-20mA/0-5V

setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network

setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal

must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded

pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be

connected at the source. When driving multiple units, each unit’s wiring must conform to the

above.

5.5.2 Direct Drive Startup

Since this mode of operation is factory preset and the valve position is being externally

controlled, no startup instructions are necessary. In this mode, the REMOTE LED will light when

the signal is present.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go

off and the MANUAL LED will light.
To change back to the Direct Drive mode, simply press the AUTO/MAN switch. The REMOTE

LED will again light and the MANUAL LED will go off.

5.6 AERCO CONTROL SYSTEM (ACS)

NOTE

ACS can utilize only RS-485 signaling to the boiler.

The ACS mode of operation is used in conjunction with an AERCO Control System. The ACS

mode is used when it is desired to operate multiple units in the most efficient manner possible.

For this mode of operation, an ACS Header Sensor must be installed between 2 and 10 feet

downstream of the LAST boiler in the boiler plant's supply water header. The ACS can control

up to 40 boilers; Up to 32 via Modbus (RS-485) network communication. For ACS programming,

operation, and Header Sensor installation details, see ACS Operations Guide, GF-131. For

operation via an RS-485 Modbus network, refer to Modbus Communication Manual GF-114.
To enable the ACS Mode, the following menu settings must be made in the Configuration Menu:

Menu Option

Setting

Boiler Mode

Direct Drive

Remote Signal

Network (RS-485)


Refer to section 3.3 for instructions on changing menu options.

5.6.1 ACS External Field Wiring

Wiring connections for RS-485 Modbus control are made between the 485 A- and 485 B+

terminals on the ACS (boilers 9 through 40) and the RS-485 COMM terminals in the I/O Box on

the front of the boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the proper

polarity for the ACS RS-485 COMM wiring connections. Shields should be terminated only at

the ACS and the boiler end must be left floating. Each unit’s wiring must conform to the above.