CHAPTER 5 – MODE OF OPERATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 71 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or

Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage

signal within the following ranges:

4-20 mA/1-5 Vdc

0-20 mA/0-5 Vdc

The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this

setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by an EMS or BAS, is used to change the unit's

setpoint. The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is equal to a

240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals described above, the Remote Setpoint mode can

also driven by a RS-485 Modbus Network signal from an EMS or BAS.
The Remote Setpoint modes of operation can be used to drive single as well as multiple units.

NOTE

If a voltage, rather than current signal is used to control the

remote setpoint, a DIP switch adjustment must be made on the

PMC Board located in the Control Panel Assembly. Contact your

local AERCO representative for details.

In order to enable the Remote Setpoint Mode, the following menu setting must be made in the

Configuration Menu:

Menu Option

Setting

Boiler Mode

Remote Setpoint

Remote Signal

4-20mA/1-5V, 0-20mA/0-5V, or Network

Refer to section 3.3 for detailed instructions on changing menu options.
If the Network setting is selected for RS-485 Modbus operation, a valid Comm Address must be

entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional

information.
While it is possible to change the settings of temperature related functions, the unit is factory

preset with settings that work well in most applications. It is suggested that an AERCO

representative be contacted, prior to changing any temperature related function settings. For

descriptions of temperature-related functions and their factory defaults, refer to Appendices A

and E.

5.4.1 Remote Setpoint Field Wiring

The only wiring connections necessary for the Remote Setpoint mode are connection of the

remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the front

panel of the boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are

made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are

made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded)

at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity

must be observed. The source end of the shield must be connected at the source. When driving

multiple units, each unit’s wiring must conform to the above.