11 ignition switch open during ignition – AERCO BMK 2000DF User Manual

Page 89

Advertising
background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 6 – SAFETY DEVICE TESTING

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 89 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

6.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the

switch, proceed as follows:

Ignition Switch Open During Ignition

1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the valve position between 25% and 30%.
3. Remove the Air/Fuel Valve cover (Figure 6-6) by rotating the cover counterclockwise to

unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-7).
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display IGN SWITCH

OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should

restart.

Figure 6-6: Air/Fuel Valve Cover Location

AIR/FUEL VALVE COVER

(Rotate Counter-Clock-Wise

to Remove)

AIR/FUEL

VALVE

BLOCKED

INLET

SWITCH

BLOWER

PROOF

SWITCH

Advertising
This manual is related to the following products: