Benchmark 1500DF - 2000DF Boilers

CHAPTER 7 – MAINTENANCE

Page 92 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

7.2 IGNITER-INJECTOR

The igniter-injector (part no. 66026) is located on the burner plate at the top of the boiler. In

addition to providing the ignition spark required to light the burner, the igniter-injector also

contains a gas injector tube which connects to the staged ignition assembly. Figure 7-1 shows

the complete burner assembly removed from the boiler and indicates the location of the igniter-

injector flame detector and other related components.

Figure 7-1: Benchmark 1500/2000 Burner Assembly (Removed from Boiler)

The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to

remove the igniter-injector from the unit after the unit has cooled to room temperature. To

inspect/replace the Igniter:

Igniter-Injector Maintenance Procedures

1.

Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

from the unit

2.

Remove the top shroud from the unit by grasping the top handle and lifting straight up.

This will disengage the shroud from the four (4) pins in the side panels.

3.

Disconnect the cable from the igniter-injector (Figure 7-1).

BLOWER

BLOWER

PLENUM

IGNITOR-

INJECTOR

ASSEMBLY

FLAME

DETECTOR

BURNER

PLENUM

FLANGE/

BURNER

TOP PLATE

FLAME

OBSERVATION

PORT

AIR/FUEL

VALVE

BLOWER

PROOF

SWITCH

O

2

SENSOR

A/F VALVE

PLENUM