AERCO SmartPlate User Manual

Page 26

Advertising
background image

SmartPlate Installation, Operation & Maintenance Manual

CHAPTER 4 – ADJUSTMENT

Page 26 of 138

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0069_0E

PRI: 11/26/2013

Phone: 800-526-0288

SP-100

COVER

SCREWS (2)

HAND-WHEEL

Figure 4-1. Control Valve Electronics Module – Top View

2. Remove the Electronics Module cover from the Valve to access the internal components

shown in Figure 4-2

1

2

3

ON

LED

AUTO-

STROKE

BUTTON

DIP SWITCHES

HAND-WHEEL

Figure 4-2. Control Valve with Electronics Module Cover Removed

NOTE

When external 120/240 VAC power is properly connected to the
ECS/SP Control Box, 24 VAC power is supplied to the MXG-461
Control Valve when the Control Box POWER switch is set to the
ON position. The POWER switch is located on the right side of the
Control Box.

3. Ensure that all three (3) DIP switches shown in Figure 4-2 are in the OFF (Down) position