AERCO SmartPlate User Manual

Page 27

Advertising
background image

SmartPlate Installation, Operation & Maintenance Manual

CHAPTER 4 – ADJUSTMENT

OMM-0069_0E

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 27 of 138

SP-100

Phone: 800-526-0288

PRI: 11/26/2013

4. Set the ECS/SP Control Box POWER switch to the ON position to apply 24 VAC power to

the Control Valve Actuator (pins 1 (G0) and 2 (G). Ensure the Valve is in the AUTO
position, the LED indicator will light green continuously indicating that Valve operation is
normal (no faults).

5. Using a pin or paper clip, depress the auto-stroke button in the opening of the terminal

housing (Figure 4-2). This will initiate calibration of the Control Valve.

6. During actuator calibration, the LED indicator (Figure 4-2) will flash green for

approximately 10 seconds. The Control Valve will be briefly closed and fully opened.

7. Upon successful completion of the Valve calibration process, the LED indicator will stop

flashing and remain ON continuously green.

8. The two-color (Red/Green) indicator is useful in determining the operating status of the

Control Valve. Refer to Table 4-1 for descriptions of the possible LED status displays
which may be encountered.

Table 4-1. Control Valve MXG-461 LED Status Indicators

LED Display

Status

Description

LED green

On continuously

Automatic Mode (normal, no faults)

Flashing

- Mechanically set to MANUAL
- Mechanically set to OFF
- Currently in Auto-Calibrate Mode

LED red

On continuously

- General fault
- General calibration fault
- Microprocessor fault

Flashing

- Faulty 24 VAC supply (Too low)

LED

Off

- No 24 VAC supply
- Electronics Module fault

9. Turn off power to the Control Valve by setting the ECS/SP Control Box POWER switch to

the OFF position.

10. Replace and secure the Electronics Module cover by tightening the two captive screws.

WARNING

MANUAL CONTROL OPERATION OF THE 3-WAY VALVE
DISABLES THE OVER-TEMPERATURE & POWER LOSS
SAFETY SHUTDOWN FEATURES OF THE SYSTEM. MANUAL
OPERATION IS ONLY USED FOR PROBLEM DIAGNOSIS.
MANUAL OPERATION MAY CAUSE OVER-HEATING OF
DOMESTIC WATER AND SCALDING OF WATER USERS.