CHAPTER 8 – CORRECTIVE MAINTENANCE
OMM-0069_0E
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
Page 83 of 138
SP-100
Phone: 800-526-0288
PRI: 11/26/2013
16. Turn ON the external circuit breaker and set the POWER Switch on the side of the
ECS/SP Control Box to the ON position to return the SmartPlate Water Heater to service
use.
Figure 8-24. Domestic Water Piping Components
8.12 STRAINERS
All SmartPlate Water Heater Models utilize Combination Strainers and Ball Valves to prevent
fouling of the Heat Exchanger by trapping foreign material before it enters the Heater. In
addition, SmartPlate provides a Differential Pressure Gauge on the Boiler Water Inlet to aid in
determining when to blow-down the Strainer. If this Gauge becomes inoperable, it should be
replaced using the following procedure.
NOTE
If normal maintenance does not clear the Water Heater flow path,
it will be necessary to remove and manually clean the screens in
the Boiler Water and DHW piping as follows:
a. Remove Strainer end cap and remove screen.