AERCO SmartPlate User Manual
Page 68

SmartPlate Installation, Operation & Maintenance Manual
CHAPTER 8 – CORRECTIVE MAINTENANCE
Page 68 of 138
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
OMM-0069_0E
PRI: 11/26/2013
Phone: 800-526-0288
SP-100
A
Figure 8-8. Measurement of Plate Pack Dimension "A"
10. If the unit is a Model SPDW113, remove the U-bolt securing the heat exchanger support
bar (see paragraph 8.9 and Figure 8-18). If the unit is a Model SPDW61, remove the U-
bolt and "L" bracket at the rear of the heat exchanger mount to permit the pressure plate
to be moved.
11. Opening of the heat exchanger is now possible by loosening diagonally-opposite pairs
(Figure 8-9). Opening must be carried out evenly so that the pressure plate is not out-of-
parallel with the frame plate by more than 3/8" (2 turns per bolt) in the horizontal plane
and 1" in the vertical plane.
Figure 8-9. Required Bolt Loosening Pattern