DIAGNOSTIC ALARMS - continued

DISPLAY MEANING

WHAT

TO

DO`

E r r 2

Error 2: RAM self-test fail

Return Controller for repair

E r r 3

Error 3: Watchdog fail

Return Controller for repair

E r r 4

Error 4: Keyboard failure.
Stuck button or button was
pressed during power-up

Switch power off and then on, without
touching any of the controller buttons

E r r 5

Error 5: Faulty internal
communication

Check printed circuit board
interconnections. If the fault cannot be
cleared, return the controller for repair.

E r r 6

Digital filter chip faulty or
loose board inside controller

Return Controller for repair

E r r 7

PV ID failure

Return Controller for repair

E r r 8

Module 1 ID failure

Faulty or loose module, or isolation
problem

E r r 9

Module 2 ID failure

Faulty or loose module, or isolation
problem

E r r A

Module 3 ID failure

Faulty or loose module, or isolation
problem

d C F

DC output failure

Return Controller for repair

O P E n

Secondary Input Missing or
Disconnected

This error may result from no power to the
flow meter (check for green power light on
rear of meter or 0-5V flowmeter signal
connections), or a disconnection of the
Molex connector between feedforward
sensor and the Eurotherm controller.

A3.1. CLEARING HARDWARE ERROR (Hw.Er) DISPLAY
To clear a Hardware Error and reset the Temperature Controller, proceed as follows:

3. Display flashes Hw.Er after adding or removing comm. bd.

4. Simultaneously press the Page (

) and Scroll (

) buttons on the Temperature

Controller.

5. Using the Up (▲) arrow button, change the password to “8”.

6. Simultaneously press the Page (

) and Scroll (

) buttons again and observe the

Temperature Controller display. The top line will display “8” and the bottom line will display
“NO”.

7. Press the Up (▲) arrow button to toggle the display from “NO” to “YES”.

8. Simultaneously press the Page (

) and Scroll (

) buttons to “Reset” the

Temperature Controller and clear the Hardware Error.