CHAPTER 8 – CORRECTIVE MAINTENANCE

OMM-0069_0E

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 75 of 138

SP-100

Phone: 800-526-0288

PRI: 11/26/2013

Figure 8-16. End Plate with Gasket Installed

8.9 DOUBLE-WALL HEAT EXCHANGER REPLACEMENT

The Heat Exchanger used in each SmartPlate Double-Wall Model is removed and replaced
using the following basic procedure:

1. Turn OFF the POWER Switch on the side of the ECS/SP Control Box.

2. Slowly close all four of the Isolation Ball Valves (Figure 8-5).

3. Connect a hose to the Strainer on the Boiler Water side of the piping assembly (Figure 8-

6). Open the valve on the Strainer and drain the boiler water from the Heater. It will be
necessary to loosen a Victaulic coupling by the Heat Exchanger to allow air into the pipe
during draining.

4. Next, connect a hose the Drain Valve on the DHW Side of the piping assembly. Remove

the 1/4” plug on the side of the Domestic Water Strainer to allow air into the pipe during
draining.

5. After the boiler water and domestic water have been drained from the Heater, replace the

1/4"plug removed in step 4 proceed to step 6 to remove the installed Heat Exchanger.

6. Using a ratchet wrench with an extension and a 3/4” deep socket, remove, the four (4)

Victaulic couplings (Figure 8-19). Two (2) couplings are located on the Domestic Water
Side and two (2) are located on the Boiler Water Side.

7. Next, remove the two (2) bolts securing the front "L" brackets on the Heat Exchanger to

the heat exchanger mount (Figure 8-17).