CHAPTER 7 – TROUBLESHOOTING

Page 50 of 138

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0069_0E

PRI: 11/26/2013

Phone: 800-526-0288

SP-100

Table 7-1. Troubleshooting – Control Valve MXG-461 and Piping Assembly – Cont.

No.

Fault Indication

Probable Cause

Corrective Action

T5

Rapid fluctuations in
heater outlet temperature
which do not follow load
changes

1. Temp. Controller is

not functioning
properly.

1. Refer to Table 7-2 and troubleshoot the

Temp. Controller.


Table 7-1A. Control Valve MXG-461 LED Status Indicators

LED Display

Status

Description

LED green

On continuously

Automatic Mode (normal, no faults)

Flashing

- Mechanically set to MANUAL
- Mechanically set to OFF
- Currently in Auto-Calibrate Mode

LED red

On continuously

- General fault
- General calibration fault
- Microprocessor fault

Flashing

- Faulty 24 VAC supply (Too low)

LED

Off

- No 24 VAC supply
- Electronics Module fault