AERCO SmartPlate User Manual

Page 79

Advertising
background image

SmartPlate Installation, Operation & Maintenance Manual

CHAPTER 8 – CORRECTIVE MAINTENANCE

OMM-0069_0E

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 79 of 138

SP-100

Phone: 800-526-0288

PRI: 11/26/2013

SECTION III SMARTPLATE WETTED COMPONENTS - ALL MODELS

8.10 CONTROL VALVE ELECTRONIC MODULE REPLACEMENT AND VALVE
REMOVAL

The only replaceable item on the 3-Way Control Valve (Siemens MXG-461) is the Electronics
Module located at the top of the Valve (Figure 8-20). The procedures for removing this Module
or replacing the complete Control Valve are provided in paragraphs 8.3.1 and 8.3.2.

Figure 8-20. Control Valve (Siemens MXG-461)

8.10.1 Electronics Module Replacement

To remove and replace the Control Valve Electronics Module:

1. Turn OFF the POWER Switch on the side of the ECS/SP Control Box.

2. Loosen the two (2) captive screws securing the Electronics Module cover (Figure 8-21).

3. Remove the Module cover to access the wiring terminals (Figure 8-22). Disconnect and

tag the power and control signal wire leads from the Module terminals.

4. Using a 3 mm Allen key, loosen the three (3) socket head screws securing the blue

Electronics Module to the black Valve Head. These socket head screws are recessed and
the Allen key must be inserted into the holes shown in Figure 8-7 to engage the screw
heads.

Advertising