Use of multiple inverter

units:

Observe the following points when using multiple inverter units on the

same power source line.

High-speed

As Shown above, there is no fuse installed in the inverter’s main

circuit, if a short circuit fault occurs in the inverter, not only MCCB2

will trip, but the main breaker MCCB1 may also trip.

Select the shut-off characteristics of MCCB1 and MCCB2 so that a

selective shutdown can be executed and only MCCB2 trips. If the

optimum characteristics cannot be selected, install a high-speed shut­

off fuse after MCCB2. (Refer to page 14 for MCCB selection.)

4.3 Inverter Disposal Precautions

Observe the following points when disposing of the inverter.

Explosions from

incineration:

Gasses from plastics:

Disposal method:

Placing the inverter in an incinerator may be dangerous, as the

electrolytic fluid used in the electrolytic capacitors may expand and

explode.

The plastic used for the cover, etc., may generate poisonous gases

when incinerated.

Commission the disposal of the inverter to a specialist.