Run frequency control

Related parameters

F r u n

Run frequency

FHy Sj frequency hysteresis

The inverter run/stop can be controlled with just the reference frequency signal. By setting the run frequency

f - u n

and the run frequency hysteresis | F H H 5 , the inverter will start running when the reference

frequency signal is higher than point B in the following diagram, and will stop when less than point A.

* For example, when using the inverter for HVAC applications, etc., and automatically operating from a room

temperature signal, the Inverter can be stopped when the reference frequency signal drops below 30Hz.

Output frequency

[H2]

Tun

Frun +

* During acceleration, the inverter will start with start-up frequency

F - 5 b

in C r-.S C when the

reference frequency signal is higher than point B. During deceleration, the inverter will stop at end frequency

F - E

n

in

C

r . 5 C

when the reference frequency signal drops below point A.