Ratings of connected

meters:

Rating of FL signal contacts:

External use of control

power:

Open collector outputs:

Frequency-setting

potentiometer:

Connect a full-scale 1 mAdc DC ammeter or full-scale 7.5Vdc-1 mA DC

voltmeter to the control terminals.

The contact rating of the protection operation detection relay (FL) is

250Vac (cos0=O.4) 30Vdc-1A.

A max. of 24Vdc-100mA can be used from the P24 control power

terminal to drive external relays.

The RCH and LOW control terminals are open-collector outputs, and

can output a max. 24Vdc-50mA. Use of a 24Vdc OMRON MY1 relay

(RY) is recommended.

Always install a diode (200V-1A class)

for surge absorption. Take special note

of the diode polarity to avoid incorrect

application.

Use a potentiometer rated at 1k to 10kO-1/4W for the frequency­

setting Input signal.

P2<

RCH

5.3 Other Precautions

Use of crimp-on terminal

lugs:

Grounding terminal:

Built-in braking resistor

Internally-connected (E)

terminal:

The clearance between terminals on the inverter main circuit terminal

block is small, so use sleeved crimp-on terminal lugs for all main

circuit terminals. Take special care during connection so that the

terminal lugs do not make contact with neighboring terminal lugs.

Always ground the G/E grounding terminal with a wire that is 3.5mm®

or larger.

For inverter capacities that are 3.7kW or less, a built-in braking

resistor is connected between the main circuit terminals (PA1) and

(PB1), providing dynamic braking as a standard feature.

The (E) terminal is for internal connections, so do not remove

connections from it or make any external connections to it.

The main circuit wiring is shown in Fig. 5.1.

(For 3.7kW or less, not showing control power terminals RO, SO)