O r . O F

(Frequency Setting Parameters)

5 r .

n

5

r.

n I

Preset speed operation ©

Related parameters

5

r-.n

Preset speed selection

5 r 0 1

5 r - 1 5

Sr-.n

Mode selection

5 r - n 1

~

S r -O F

Operating frequency settings

Operating mode settings

By changing external contact signal inputs, a max. of 15 preset speeds can be selected. (Refer to

C

r-. 5

fc I

f h

*

I

for terminal allocation.)

Each speed (frequency) can be set between 0 and 400Hz.

* Note that the preset speeds cannot be set higher than the value of the max frequency | F H | • so the value

of

FH

I

must also be changed if a higher preset speed is desired.

Basic setting method

1, Select the desired No. of speeds for preset speed operation.

S r . n ■ 0

: disabled

/~ iS : Speeds 1 to 15

2 . Select the operating mode. I

5^ /-j

5»- r? *

U : Deactivated

/ : Activated

0 : Acc/dec #1, V/F#1, forward run

+ / : Reverse run selection

+ F : Acc/dec #2 selection

+

: V/F #2 selection

* Data setting of parameters indicated as using the *+■ mark is as follows:

Example) (+ / ) + (+P) = 3

Both reverse run and Acc/Dec #2 will be in effect when

3

is selected.

3. Set the operating frequencies for the applicable speeds between the lower limit and upper limit frequencies.

S r - O I

1 5

4. Allocate the terminals for preset speed operation.

(*: D t o 1 0 ).)

(Refer to O r . 5 1 I t *

Preset speed No.

Terminal signal

Normal

frequency
command

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

SSI

0

0

0

0

0

0

0

0

SS2

0

0

0

0

0

0

0

0

SS3

0

0

0

0

0

0

0

0

SS4

0

0

0

0

0

0

0

0

(— = terminal-CC open, O = terminal-CC closed)

- 67 -