Minimum system configurations for ul installations, Specifications – Interlogix NX-6V2 REV B Installation Manual User Manual
Page 8

WARNING:
Electrical codes will vary, depending on the
country and city where the system is installed. It is the
installers responsibility to ensure that the electrical installation
is safe and conforms to all applicable codes , laws, and
regulations. Only qualified persons should connect this device
to the main supply.
Minimum system configurations for UL installations
The following requirements apply to residential fire, residential
burglary, and commercial burglary installations.
•
The NetworX NX-6V2 panel is necessary to initiate
residential and commercial installations.
•
At least one compatible keypad is needed for all
applications.
•
The AD10-12 bell and UL Approved bell-housing shall be
used for all applications.
•
Commercial UL applications require the NX-003-C metal
enclosure. Supplied screws to be used.
•
A minimum of two keypads is required for home health
applications, and each keypad must be set to a unique
address.
•
The wireless devices are only UL listed for residential
applications.
•
The DACT shall be enabled for all commercial burglary
applications.
UL requires that an alarm panel work for a minimum amount of
time during a power failure.
lists the battery capacities
needed to meet time limits based on the current draw of the
panel and all attached devices.
Table 6. Battery capacities
Standby time
Total
auxiliary
current
Standby
battery
capacity
Alarm current
24-Hours 1.9
A
1.25 A
600 mA
51 Ah
34 Ah
17 Ah
600 mA
1 A
1 A
48-Hours 900
mA
600 mA
300 mA
51 Ah
34 Ah
17 Ah
1 A
1 A
1 A
72-Hours 600
mA
400 mA
200 mA
51 Ah
34 Ah
17 Ah
1 A
1 A
1A
Note: Calculations are based on three 17A batteries.
WARNING:
Replace only with a Panasonic LC12V4BP or
Yuasa NP4-12 battery. There is a risk of explosion if the
battery is replaced with an incorrect type.
WARNING:
If separate power supplies are necessary to
accommodate additional devices, safety standards require that
each power supply be prominently marked with adequate
instructions for removing all power from the unit.
Caution:
Observe polarity when installing a new battery.
Installing the battery backwards may cause damage to the
panel. Dispose of used batteries according to the
manufacturer’s instructions and/or local government
authorities.
Specifications
Operating power
16.5 VAC 40 or 50 VA transformer
Auxiliary power w/25
VA transformer
12 VDC regulated 500 mA
Auxiliary power w/40 ro
50 VA transformer (M
G Electronics part
number 22-156 for UL
or 22-156-CN for
Canadian installations)
12 VDC regulated 1 A
Loop resistance
Standard loop
300 ohms maximum
Fuse
Type T 200 mA 250 VAC
Built-in siren driver
Two tone (temporal and yelp)
Loop response
Selectable 50 mS or 500 mS
Operating temperature
32 to 120°F (0 to 49°C)
LED keypad
• Current
draw
•
Zones normal w/o
sounder
• Dimensions
•
130 mA max.
• 55
mA
•
6.4 x 4.0 x 1.1 in. (16.3 x 10.2 x 2.8 cm)
LED keypad
• Current
draw
•
Zones normal w/o
sounder
• Dimensions
•
110 mA max.
• 75
mA
•
6.4 x 5.3 x 1.0 in. (16.3 x 13.5 x 2.5 cm)
Metal enclosure
dimension
11.25 x 11.25 x 3.50 in. (28.58 x 28.58 x 8.90
cm)
Shipping weight
9 lb. (4.1 kg)
8
NX-6V2 Control Panel Installation Instructions