App1, Appendix 1 - error codes (continued) – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 106

Advertising
background image

96

Service Manual - NeoTherm 500

Appendix 1 - Error Codes (continued)

Code

Description

L or H Procedure

129

Fan speed failed during preignition

H or L 1. Check wiring and correct any potential wiring errors.

See Section B22.
2. Check the VFD’s (Variable-speed Fan Drive) ability

to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

130

Fan speed failed during ignition

H or L 1. Check wiring and correct any potential wiring errors.

See Section B22.
2. Check the VFD’s (Variable-speed Fan Drive) ability

to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

131

Fan movement detected during standby

H

1. Check wiring and correct any potential wiring errors.

See Section B22.
2. Check the VFD’s (Variable-speed Fan Drive) ability

to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

132

Fan speed failed during run

H

1. Check wiring and correct any potential wiring errors.

See Section B22.
2. Check the VFD’s (Variable-speed Fan Drive) ability

to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

137

ILK (Interlock) failed to close

H

1. Check wiring and correct any possible shorts.
2. Check interlock (ILK) switches to assure proper func-

tion.
3. Verify voltage through the interlock string to the inter-

lock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace

the module.

149

Flame detected

H or L Holds if flame detected during safe start check up to

flame establishing period.

150

Flame not detected

H

Sequence returns to standby and restarts sequence

at the beginning of purge after the HF switch opens

if flame detected during safe start check up to flame

establishing period.

152

Combustion pressure on

H or L 1. Check wiring and correct any errors.

2. Inspect the combustion pressure switch to make sure

it is working correctly.
3. Reset and sequence the relay module.
4. During standby and prepurge measure the volt-

age between J6 terminal 5 and L2 (N). Supply voltage

should be present. If not, the lockout switch is defective

and needs replacing.
5. If the fault persists, replace the relay module.

App1

cont.

Advertising
This manual is related to the following products: