LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 44

Advertising
background image

34

Service Manual - NeoTherm 500

For the low gas pressure switch only -

Mark the wire on the left using a piece of electri-

cal tape. When the switch is assembled, this

wire will go to the “N.O.” connection.

Wire to N.O.

contact

Mark this

wire with a

piece of tape.

Fig. B15-4 - Low gas pressure switch - cover removed

5. Remove the switch using the two wrenches.

For the high gas pressure switch only -

Turn the red knob on the gas valve so it is in a

vertical position. This will give you more room to

use the wrenches.

6. To reassemble, reverse the procedure we have

just described. Use gas-resistant pipe dope or

Teflon® tape on the threaded joints. For both the

high gas pressure and low gas pressure switch-

es, check the setting on the adjusting knob. Both

switches should be set to 3” w.c..

Important! Remember to reset the low-pressure

switch before you place the NT unit in operation.

(Every low pressure switch will need to be reset

when it arrives from the factory.) To reset, press

the black rubber-booted button to the left of the

adjusting knob.

7. After reassembly, check for gas leaks using leak

detection solution (i.e. Hercules Megabubble® or

equivalent).

Set to

3” w.c.

B15

cont.

Removing and Replacing the High and Low

Gas Pressure Switches (continued)