Checking the Safety Chain - continued

B3

cont.

24V AC is

present?

(other safety

switches closed)

Yes

No

Check for 24V AC at

terminal J6-1.

With boiler attempting to run,

check for 24V AC across

two leads on air pressure switch.

24V AC is

present?

(switch open)

Yes

See procedure B16 -

“Checking Condensate Trap Level Switch”

No

12185

See procedure B19 -

“Checking the Air Pressure Switch”

NT unit should be trying to fire.

If not firing, control panel should

be displaying an error code.

See Error Codes in Appendix.

2-12