B19 - checking the air pressure switch, Checking the air pressure switch, Blower proving switch – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual
Page 48: See section b19, Checking the air, Pressure switch, If the pressure switch remains open, go to sec, Tion b19, “checking the air pressure switch, See procedure b19
Advertising
38
Service Manual - NeoTherm 500
Exhaust vent
blocked?
Yes
No
Clear the vents.
Check the bird screens
or terminals.
Check for blocked air intake
and exhaust vents.
Clean with a shop-vac.
Dirty fan?
Yes
No
Switch is OK?
No
Replace switch.
Yes
Problem with
blower?
Yes
No
Heat exchanger
is plugged?
Yes
B19
Checking the Air Pressure Switch - Blower Proving Switch