67

Service Manual - NeoTherm 500

Cleaning the Burner and Heat Exchanger (continued)

C5

cont.

6. Disconnect the wires to the blower. See Fig. C5-5.

There are two connectors. The power wires run to

the front connector, and the control wires connect to

the rear.

7. The next job is to separate the front plate on the

heat exchanger from the rest of the unit. See Fig.

C5-6. Note the two large wires running to this as-

sembly. The spark wire and the flame sense wire

look alike. The unit will not run if you reverse

these wires. Before removing the wires, mark the

spark wire with a piece of electrical tape. Also dis-

connect the green ground wire.

Ground wire

(green)

Spark wire - mark with

electrical tape

Flame sense

wire

Power

Control

Fig. C5-5 - Wiring connectors for blower

Fig. C5-6 - Disconnect the wires on the front plate of the

heat exchanger