Removing and replacing the flow switch (continued) – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 35

Advertising
background image

25

Service Manual - NeoTherm 500

Removing and Replacing the Flow Switch (continued)

7. Once you have trimmed the paddles, install them

on the switch. See Fig. B10-1. Insert the pin to

attach the paddles to the center post.

8. Important! When the switch is installed, the ends

of the paddles must sit in the correct orientation

inside the pipe. The paddles must be placed so

they can sense the water flow, and they can bend

with the direction of the water flow.
• The wide sections of the paddles must sit

across the line of the water flow, partially block-

ing the flow.

• The flowing water should hit the longer paddle

first. See Fig. B10-1.

9. Note the arrow and the word “Flow” on the large

mounting nut. This will help you to install the

paddles in the correct orientation.

10. Coat the threads with pipe dope or Teflon® tape

and install the part.

Important! With the pipe wrench, tighten so the

paddles sit in the orientation shown above. Be

sure the arrow on the large mounting nut points

in the direction of water flow.

11. Re-connect the wires as shown in Fig. B9-3.
12. Open the water isolation valves and check for a

leak where the switch is threaded into the pipe.

13. Turn on power to the unit.

Paddles

Direction of

water flow

Pin

Fig. B10-1 - Attaching the paddles

B10

cont.

FLOW

Advertising
This manual is related to the following products: