LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 31

Advertising
background image

21

Service Manual - NeoTherm 500

Procedure - Replacing the control box
1. To remove the cover, remove the two sheet metal

screws on the sides.

2. Disconnect the three wires on the terminal strip,

and the violet wire that runs to the connector

above the terminal strip. See Fig. B6-2.

3. The control box is attached to the backing plate

by two sheet-metal screws with large heads. See

Fig. B6-3. One of these holds the green ground

wire. Use the 5/16” socket to loosen both of

these. Remove the green ground wire from the

left-hand screw. Twist the box slightly and pull it

away from the backing plate.

4. To reassemble, reverse the procedure we have

just described. Remember to attach the green

ground wire to the inner sheet metal screw (5/16”

head).

Fig. B6-2 - Connections to low water

cutoff control

Fig. B6-3 - Control for low water cutoff with cover removed

These two screws

attach the control box

to the mounting plate.

Removing and Replacing the Low Water Cutoff Controls (cont.)

B6

cont.

A

P2 - Black with orange stripe

P1 - Brown with yellow stripe

1

2 - White

Advertising
This manual is related to the following products: