Cleaning the burner and heat exchanger (continued) – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 76

Advertising
background image

66

Service Manual - NeoTherm 500

Disassembly Procedure:
1. Turn off power to the machine. Use the main discon-

nect switch on the front of the machine, just above

the control panel.

2. Remove the front panel.
3. Shut off the gas at the gas shutoff valve on the right

side of the machine (yellow handle).

4. On the left end of the gas valve assembly, remove

the four bolts which attach the gas valve assembly

to the blower. See Fig. C5-3. The 5/16” socket will

fit the head of each bolt. Use the 3/8” socket on the

nut on the other end.

5. Behind the gas valve, locate the black rubber air

intake hose. Loosen the hose clamp on the left end

of this hose, and pull the end of the hose away from

the end of the Venturi. Fig. C5-4 shows how the unit

will look when you have finished this step.

Fig. C5-2 - Gas shutoff valve (typical)

Cleaning the Burner and Heat Exchanger (continued)

C5

cont.

Undo these

bolts

Fig. C5-3 - Undo the four bolts at the left end of the

assembly

Fig. C5-4 - Gas and air intakes disconnected

Advertising