Service Manual - NeoTherm 500

10. Check for 24V AC between terminal J6-1 on the

control module and any terminal on TB4. See

Fig. B1-6. If 24V AC is present here, this means

that the following safety switches are OK:

• High gas pressure switch

• Low gas pressure switch

• Condensate trap level switch

If 24V AC is not present, troubleshoot the three

components:

• Section B12 - High Gas Pressure Switch

• Section B13 - Low Gas Pressure Switch

• Section B16 - Condensate Trap Level Switch

11. If you see 24V AC at J6-1, this means that all

of the switches in the safety chain are satisfied.

The blower should run, and then the pressure

switch should close, allowing the ignition se-

quence to start. To check the pressure switch,

check for continuity (no resistance) between ter-

minal 1 on J6 and terminal 1 on J5 on the control

module. See Fig. B1-7.

If the pressure switch remains open, go to Sec-

tion B19, “Checking the Air Pressure Switch.”

Fig. B1-6 - Checking the safety switches

Fig. B1-7 - Checking the safety switches

Quick Check of Components in the

Safety Chain - continued

B1

cont.

J6-1

J5-1

J6-1