Using the current user interface - continued – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 93

Advertising
background image

83

Service Manual - NeoTherm 500

Fig. D5-8 - Enable/ disable screen

Fig. D5-9 – Changing LCD contrast

Turning a Function On and Off
Some of the values can be enabled or disabled. Figure

D5-8 shows one example.
• Use the Up- and Down-Arrows to highlight the line

you want, then press the round OK button.

Changing a Value Using a “Slider”
There is another type of control screen you may see.

This type of screen uses a “slider” to set the value. This

system is used on the LCD Contrast screen (available
under Display Setup.) See Fig. D5-9.
• Use the Left- and Right-Arrow buttons to move the

bar and adjust the contrast.

• When the setting is correct, press the round OK

button.

Using the Diagnostics -
Use the Diagnostics to check the status of the sensors

and the digital inputs and outputs. The system also

records a history of lockouts and alarms.
Analog Sensors -You can use this display to check on

operating temperatures, fan speed, firing rate, etc. (The

word “analog” refers to values that can change continu-

ously between zero and a higher value.) The values

shown here are “Read Only” – you can’t change them

from this display.
Digital Input/Output -This display shows whether differ-

ent functions, inputs and outputs are either on or off.

The functions listed here include pumps, valves, alarms,

etc. The values shown here are “Read Only” – you can’t

change them from this display.
History - The system records the most recent lockouts or

alerts. (If there is a current lockout or alert, a note about
this will also appear at the bottom of the Home screen.)

Using the Current User Interface - continued

D5

cont.

Advertising
This manual is related to the following products: