LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 12

Advertising
background image

LAARS Heating Systems

Page 12

When the unit is vented through the roof, the

vent must extend at least 3 feet (0.9m) above the point

at which it penetrates the roof. It must extend at least

2 feet (0.6m) higher than any portion of a building

within a horizontal distance of 10 feet (3.0m), and high

enough above the roof line to prevent blockage from

snow. When the combustion air is taken from the roof,

the combustion air must terminate at least 12" (30cm)

below the vent terminal (

see Figure 2

).

2.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must

be used to prevent entry of rain water (

see Figure 2

).

The opening on the end of the terminal must be at least

12" (30cm) above the point at which it penetrates the

roof, and high enough above the roof line to prevent

blockage from snow. When the vent terminates on the

roof, the combustion air must terminate at least 12"

(30cm) below the vent terminal.

2.4 Common Vent Test — Boilers

When an existing boiler is removed from a

common venting system, the common venting system

is likely to be too large for proper venting of the

appliances remaining connected to it.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances

remaining connected to the common venting system

are not in operation.

1. Seal any unused openings in the common venting

system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is

no blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe

condition.

3. Insofar as it is practical, close all building doors

and windows and all doors between the space in

which the appliances remaining connected to the

common venting system are located and other

spaces of the building. Turn on clothes dryers

and any appliance not connected to the common

venting system. Turn on any exhaust fans, such

as range hoods and bathroom exhausts, so they

will operate at maximum speed. Do not operate a

summer exhaust fan. Close fireplace dampers.

4. Place in operation the appliance being

inspected. Follow the lighting instructions.

Adjust thermostat so appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening

after 5 minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting

system properly vents when tested as outlined

above, return doors, windows, exhaust fans,

fireplace dampers and any other gas burning

appliance to their previous conditions of use.

7. Any improper operation of the common venting

system should be corrected so that the installation

conforms to the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and/or CSA B149.1, Installation

Codes. When resizing any portion of the common

venting system, the common venting system

should be resized to approach the minimum size

as determined using the appropriate tables in Part

II of the National Fuel Gas Code, ANSI Z223.1/

NFPA 54 and/or CSA B149.1, Installation Codes.

2.5 Vent Terminals for Outdoor Units

For outdoor applications, the vent and

combustion air openings must be covered with proper

terminals to prevent rain, snow and other objects from

falling into the Pennant.

If local codes allow, outdoor installations may

use 1' of appropriately sized galvanized single wall

or B-Vent and a rain cap for exhaust vent termination

in the default configuration (venting out of the top).

An appropriately sized galvanized 90° ell, positioned

with the opening facing down, may be used on the

combustion air inlet in the default configuration on

the back of the unit. Note that some local codes may

require a higher vertical vent height, extending above

any perimeter fencing, etc. In installations where the

appearance of the vent is objectionable, the low profile

vent terminals in

Table 6

may be used.

Part numbers for the low profile terminals to

cover the vent and combustion air openings are shown

in

Table 6

.

OUTDOOR

OUTDOOR

SIZE

VENT

COMBUSTION

TERMINAL

AIR TERMINAL

500

20254703

D2007900

750

20254705

D2007900

1000

20254705

D2008000

1250

D2007700

D2008000

1500

D2007700

D2008000

1750

D2007800

D2008000

2000

D2007800

D2008200

Table 6. Vent Terminals for Outdoor Units.

Advertising
This manual is related to the following products: