SECTION 7.

Maintenance

7.1 System Maintenance

1. Lubricate the system water-circulating pump, if

required, per the instructions on the pump.

2. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.

3. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean

the screens in the vent terminal and combustion

air terminal (when used).

4. Keep the appliance area clear and free from

combustible materials, gasoline, and other

flammable vapors and liquids.

5. If the appliance is not going to be used for

extended periods in locations where freezing

normally occurs, it should be isolated from the

system and completely drained of all water. All

systems connected to it should also be drained or

protected from freezing.

6. Low water cutoffs, if installed, should be

checked every 6 months. Float type low water

cutoff should be flushed periodically.

7. Inspect flue passages, and clean with brushes/

vacuums, if necessary. Sooting in flue passages

indicates improper combustion. Determine the

cause and correct.

8. Inspect the vent system and air intake system,

and if the vent system is Category III, ensure that

all joints are sealed properly. If joints need to

be resealed, completely remove existing sealing

material, and clean with alcohol. Apply new

sealing material, and re-assemble.

7.2 Appliance Maintenance and

Component Description

Only genuine Laars replacement parts should be used.

Caution

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing.

See

Figures 31 and 32

for location of gas train

and control components.

The gas and electric controls on the appliance

are engineered for long life and dependable operation,

but the safety of the equipment depends on their

proper functioning. It is strongly recommended that

a qualified service technician inspect the basic items

listed below every year:

a. Ignition controls

d. Automatic gas valve

b. Ignitors

e. Pressure switches

c. Water temperature

f. Blowers

control

7.2.1 Burners

Close main manual gas valve before proceeding.

Checking the burners for debris - Remove the ignitor

inspection panels(s) and ignitor(s) and inspect the

burners through the ignitor hole(s) using a flashlight

to illuminate. If there is any indication of debris on

the burners that are visible, all the burners will need

to be inspected more thoroughly. Remove the screws

from around the front of the air box (large panel from

which the ignitor inspection panel(s) were removed),

and remove the large panel. Remove the gas manifold

assemblies and the burner panels. Inspect the burners.

Clean burners, if necessary, by blowing compressed

air from the outside of the burners into the center

of the burner. A dirty burner may be an indication

of improper combustion or dirty combustion air.

Determine the cause, and correct. Replace the burners

in the reverse order

7.2.2 Filter

The filter used in the Pennant is washable with

an 83% arrestance. Since the filter is washable, it will

only need replacement when unwashable, deteriorated

or damaged. If filter replacement is needed, it should

only be replaced with a factory part. Inspect the air

filter. If there is debris on the air filter, remove it from

the filter box, and wash it with mild soap and water.

Ensure that the filter is completely dry before re-

installing, in reverse order.

7.2.3 Gas Valves

The gas valves are designed to operate with

supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).

To remove a valve, shut off 120-volt power

and the manual gas shutoff valve. Remove the top

front panel from the unit. Disconnect the wires to the

valve. Disengage the flanged fitting before and after

the valve, and remove the valve. Re-install in reverse

order. Ensure o-rings are properly installed for both

inlet and outlet. Turn on manual gas shutoff valve and

120 volt power and check appliance operation and

tightness of gas valve connections.

7.2.4 Manual Reset High Limit Control

The high limit switch is manual reset switch with

an adjustable set point, up to 240°F (116°C) on boiler

models and 200°F (93°C) on water heater models

and boilers ordered with low temperature controls. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull the

switch off the control panel. Remove the capilliary

and bulb from the thermal well located in the header.

Replace in reverse order.

7.2.5 Automatic Reset High Limit Control

An automatic reset high limit is used in addition

to the manual reset high limit. The high limit switch

has an adjustable set point, up to 240°F (116°C) on

boiler models and 200°F (93°C) water heater models