LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 46

Advertising
background image

LAARS Heating Systems

Page 46

6.4.10 External Boiler Operation

When mode 6 is selected, the control allows for

an external control to operate the Pennant’s stages. In

this mode, the control operates the pump in order to

provide purging and exercising. The staging operation

is provided by an external device such as an Energy

Management System (EMS) or External Staging

Control.

Heat Demand – A heat demand is generated

when stage one is wired properly, and the external

control closes the contacts on the stage one terminals

(1C-1NO), calling the Pennant for heat. The Pennant

is shipped with a jumper between the Com D and Ht D

terminals, and this jumper must remain in place when

and external control is providing the heat demand

signal to these terminals. The control energizes the

boiler pump (if equipped), energizes the Pmp-Pmp

terminals, and turns on the boiler pump segment in the

display. The control also turns on stage 1 of the boiler.

Section 5.3

contains important information about

external staging controls and building automation

systems. Other wiring methods may be unsafe. The

wiring in

Section 5.3

of this manual must be used.

6.4.11 Limit Controls

In addition to the temperature control, Pennant

appliances are fitted with a manual reset high limit and

an automatic reset high limit. These are located near

the rear of the cabinet on the right side, behind the

slide out drawer (see

Figure 32

). Both controls should

be set at least 25°F higher than the target temperature

to avoid short cycling. To set these controls, remove

the control panel cover and pull the control panel

out to gain access. Appliances with reversed heat

exchangers have the limit controls relocated to the left

side of the appliance. The left access door must be

removed to gain access to the limit controls on these

appliances.

6.4.12 Advanced Programming Mode

Advanced programming mode allows the

installer to set the temperature control for proportional

staging. In advanced programming mode, the

interstage differential, interstage delay, interstage on

and off delay, and minimum time on and off are all set

manually.

NOTE: Advanced programming mode is rarely

required. It is intended for advanced installers,

and only when the application demands such

programming.

To enter advanced programming mode, remove

the bezel on the temperature control by pulling out at

the bottom. Remove the small phillips head screw to

access the dip switch. The dip switch is mounted on a

circuit board.

Locate the letter “A” on the circuit board and

slide the corresponding dip switch toward the letter

“A”. The default setting of this dip switch is toward

the

OFF

lettering on the circuit board.

6.5 Operating the Burner and Set Up

6.5.1 Set Up for 0 to 2500 Feet Altitude

The Pennant appliance utilizes a modular design

to achieve its stage-firing. The setup must be checked

before the unit is put in operation. Problems such as

failure to start, rough ignition, strong exhaust odors,

etc. can be due to improper setup. Damage to the

Pennant resulting from improper setup is not covered

by the limited warranty.

1. Using this manual, make sure the installation

is complete and fully in compliance with the

instructions.

2. Determine that the appliance and system are

filled with water and all air has been bled from

both. Open all valves.

3. Observe all warnings on the Operating

Instructions label and turn on gas and electrical

power to appliance.

4. Switch on the appliance power switch located on

the right side of the unit.

5. The Pennant will enter the start sequence, as long

as the unit is being called for heat. The blower

and pump come on for pre-purge, then the ignitor

warm-up sequence starts and after the ignitor

warm-up is complete and all safety devices are

verified, the gas valves open. If ignition doesn’t

occur, check that there is proper gas supply.

Wait 5 minutes and start the unit again. During

initial start up, air in the gas line may cause the

Pennant to "lock out" during the first few trials

for ignition. Depending on the ignition modules

installed, the manual reset button on the ignition

modules may need to be depressed to restart the

Pennant.

6. When the unit is running, the supply gas pressure

must be checked. Inlet gas pressure must not

exceed 13" w.c. (3.2kPa). The minimum inlet gas

pressure is 5" w.c. (1.2kPa).

7. Once the inlet gas pressure is verified, the

outlet gas pressure from each valve (manifold

gas pressure) must be checked, and adjusted, if

necessary. The manifold gas pressure must be

2.5" w.c. (0.62kPa).

8. Complete the setup by checking the CO

2

at the

outlet of the unit. The CO

2

should be 8% for

natural gas, or 9.2% for propane.

9. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested.

To test:

(a) Close gas shutoff valve with burner

operating.

(b) The flame will go out and blower will

continue to run for the post purge cycle.

One additional attempt to light will follow.

Ignition will not occur as the gas is off. The

ignition control will lockout, and will have

to be reset before the unit will operate.

Advertising
This manual is related to the following products: