LAARS Heating Systems

Page 8

Figure 2. Combustion Air and Vent Through Roof.

EACH OPENING*

SIZE

SQUARE INCHES

SQUARE CM

500

125

807

750

188

1213

1000

250

1613

1250

313

2020

1500

375

2420

1750

438

2826

2000

500

3226

*Net Free Area in Square Inches / Square cm

Area indicated is for one of two openings; one at floor level and

one at the ceiling, so the total net free area could be double the

figures indicated.
This chart is for use when communicating directly with the

outdoors. For special conditions and alternate methods, refer to

the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of

louvers. Correct for screen resistance to the net free area

if a screen is installed. Check all local codes applicable to

combustion air.

Table 3. Combustion Air Openings.

SECTION 2.

Venting and Combustion Air

2.1 Combustion Air

Pennant boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with Section 5.3, Air for Combustion and

Ventilation, of the National Fuel Gas Code, ANSI

Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,

Installation Codes, or applicable provisions of the local

building codes.

A Pennant appliance may receive combustion

air from the space in which it is installed, or it can be

ducted directly to the unit from the outside. Ventilation

air must be provided in either case.

2.1.1 Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of

the same cross-sectional area as the free area of the

openings to which they connect.

Method 1: Two permanent openings, one

commencing within 12 inches (30 cm) of the top

and one commencing within 12 inches (30 cm) of

the bottom, of the enclosure shall be provided. The

openings shall communicate directly, or by ducts,

with the outdoors or spaces that freely communicate

with the outdoors. When directly communicating

with the outdoors, or when communicating to the

outdoors through vertical ducts, each opening shall

have a minimum free area of 1 square inch per 4000

Btu/hr (5.5 square cm/kW) of total input rating of all

equipment in the enclosure. When communicating to

the outdoors through horizontal ducts, each opening

shall have a minimum free area of not less than

1 square inch per 2000 Btu/hr (11 square cm/kW) of

total input rating of all equipment in the enclosure.

Table 3

shows data for this sizing method, for each

Pennant model.

Method 2: One permanent opening, commencing

within 12 inches (30 cm) of the top of the enclosure,

shall be permitted. The opening shall directly

communicate with the outdoors or shall communicate

through a vertical or horizontal duct to the outdoors

or spaces that directly communicate with the outdoors

and shall have a minimum free area of 1 square inch

per 3000 Btu/hr (7 square cm/kW) of the total input

rating of all equipment located in the enclosure. This

opening must not be less than the sum of the areas of

all vent connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform

to the requirements in the applicable codes listed

above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow CSA

B149.1.

2.1.2 Intake Combustion Air

The combustion air can be taken through the

wall, or through the roof. When taken from the wall, it

must be taken from out-of-doors by means of the Laars

horizontal wall terminal (see

Table 2

). When taken

from the roof, a field-supplied rain cap or an elbow

arrangement must be used to prevent entry of rain

water (

see Figure 2

).

Use single-wall galvanized pipe, per

Table 4

, for

the combustion air intake (see

Table 2

for appropriate

size). Route the intake to the heater as directly as

possible. Seal all joints with tape. Provide adequate

hangers. The unit must not support the weight of the

combustion air intake pipe. Maximum linear pipe