LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 44

Advertising
background image

LAARS Heating Systems

Page 44

Figure 30. Temperature Control Outdoor Start Graph.

selected, pump operation is continuous. Also, during

outdoor reset, with the pump delay set to

ON

, the pump

continues to run even during Warm Weather Shut

Down.

6.4.7 Setpoint Operation

When either mode 1 or 2 is selected, the control

controls the water temperature based on a fixed

setpoint. The setpoint temperature is set using the

BOIL TARGET item in the ADJUST menu.

Heat Demand – For “heat demand” to exist,

there must be continuity between the Com D (common

demand) and the Ht D (heat demand) terminals. The

Pennant ships with a jumper between these terminals.

The control also evaluates the sensor(s) installed

in the system, including the outlet sensor provided on

the boiler when using mode 1. When the control senses

continuity between Com D and Ht D terminals, and

that the sensor reading is below the target temperature,

the control will activate the Dem segment in the

display.

The control energizes the pump (on pump

mounted boilers) and energizes the Pmp Pmp

terminals. The boiler pump segment is turned on in

the display. The control then operates the stages to

maintain the setpoint temperature.

6.4.8 Dedicated Domestic Hot Water

When mode 3 is selected, the control provides

dedicated domestic hot water operation.

Internal DHW Demand – A sensor is required

to be connected on the SC2 and Sup/S terminals.

An internal demand for DHW is generated when the

temperature demand for DHW sensor drops ½ of the

tank differential setting below the desired DHW tank

temperature. The

TANK TARGET setting is used to

set the desired DHW tank temperature.

Once an internal demand is generated, the

Dem segment turns on in the LCD. The control then

closes the Pmp Pmp contact, which starts the pump

and the control turns on the boiler pump segment in

the display. The control then operates the stages to

maintain the programmed boiler target temperature at

the boiler outlet sensor.

The boiler target temperature is set using the

BOIL TARGET item in the Adjust menu. NOTE:

External demand is not required in this mode of

operation.

Tank Differential – A differential setting that

operates ½ above and below the

TANK TARGET is

selectable using the

TANK DIFF item in the Adjust

menu.

6.4.9 Outdoor Reset Operation

When either mode 4 or 5 is selected, the control

uses outdoor reset to control the water temperature.

Outdoor reset adjusts the target temperature based

on the outdoor air temperature and reset ratio. The

reset ratio is determined from the Boiler Start, Boiler

Design, Outdoor Start and Outdoor Design settings.

Heat Demand – For “heat demand” to exist,

there must be continuity between the Com D (common

demand) and the Ht D (heat demand) terminals. The

Pennant ships with a jumper between these terminals.

The control also evaluates the sensor(s) installed

in the system. If the control is not in warm weather

shutdown (WWSD), and the sensor(s) are below the

target temperature, the Dem segment is turned on

in the display. The control energizes the pump (on

pump mounted boilers) and energizes the Pmp-Pmp

terminals, and the boiler pump segment is turned on

in the display. The control then operates the stages to

maintain the setpoint temperature.

Boiler Start (BOIL START) – The BOIL

START temperature is the theoretical boiler supply

water temperature that the heating system requires

when the outdoor air temperature equals the OUTDR

START temperature setting. The BOIL START is

typically set to the desired building temperature (see

Figure 30).

Outdoor Start (OUTDR START) – The

OUTDR START temperature is the outdoor air

temperature at which the control provides the BOIL

START water temperature to the system. The OUTDR

START is typically set to the desired building

temperature.

Outdoor Design (OUTDR DSGN) – The

OUTDR DSGN is the outdoor air temperature that is

the typical coldest temperature of the year where the

building is located. This temperature is used when

doing heat loss calculations for the building.

Boiler Design (BOIL DSGN) – The BOIL

Advertising
This manual is related to the following products: