1.6 Locating Pump-Mounted Water Heater

with Respect to Storage Tank(s)

For best results, a pump-mounted Pennant water

heater should be located within 15 feet (4.6m) of the

storage tank(s). The pump is sized for 30 feet (9.1m)

of piping.

If the appliance must be installed with longer

piping runs, then larger diameter pipe or tubing shall

be used. Consult the factory for assistance.

1.7 Locating Pump-Mounted Boiler with

Respect to Return/Supply Header

For the best results, a pump-mounted Pennant

Boiler should be located within 15 feet (4.6m) of the

supply and return headers. The pump is sized for 30

feet (9.1m) of piping.

If the appliance must be installed with longer

piping runs, then larger diameter tubing shall be used.

Consult the factory for assistance.

HORIZONTAL

AIR COLLAR

VENT COLLAR

VENT PIPE

& PIPE

MAX. PIPE

MAX. NO.

SIDE WALL

SIDE WALL

SIZE

SIZE

DIAMETER

DIAMETER

LENGTH

OF ELBOWS

VENT

COMBUSTION

TERMINAL

AIR

TERMINAL

in.

cm

in.

cm

in. cm

ft. m

PART NUMBER

PART NUMBER

500

8

20

6

15

6

15

50 15

3 CA001401 20260701

750

10

25

8

20

6

15

50 15

3 CA001402 20260701

1000

10

25

8

20

8

20

50 15

3 CA001402 20260703

1250

12

30

8

20

8

20

50 15

3 CA001403 20260703

1500

12

30

8

20

8

20

50 15

3 CA001403 20260703

1750

14

36

8

20

8

20

50 15

3 CA001403 20260703

2000

14

36

12

30

12 30

50 15

3 CA001404 20260706

Table 2. Horizontal Vent / Combustion Air Parameters.

1.8 Locating Appliance for Correct

Horizontal Vent/Ducted Air Distance

From Outside Wall

The forced draft combustion air blower/blowers

in the appliance has/have sufficient power to pull air

and vent properly when the following guidelines for

horizontal air and vent are followed (

see Table 2

).

NOTE: On all model sizes, the vent collar size is

larger than the size of the vent pipe that can be used.

Vent collar size and horizontal pipe diameters can

be found in

Table 2

. The larger vent collar size is to

accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the Pennant

combustion air intake terminal must be installed

a minimum of 12" (30cm) below the exhaust vent

terminal and separated by a minimum of 36 inches

(91cm) horizontally.

The air intake terminal must be installed high

enough to avoid blockage from snow, leaves and other

debris.

REQUIRED

RECOMMENDED

APPLIANCE

CLEARANCE FROM

SERVICE ACCESS

SURFACE

COMBUSTIBLE MATERIAL

CLEARANCE

inches

cm

inches

cm

Left Side

1

2.5

24

61

Right Side

1

2.5

24

61

Top

1

2.5

12 30

Back

1

2.5

**

12**

30**

Front

1

2.5

36

91

Vertical

(Category 1)

6*

15.2*

Vent

Horizontal

per UL1738 venting

(Category 3)

system supplier’s

Vent

instructions

*1" (2.5cm) when b-vent is used.

**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).

Table 1. Clearances.